EMH
Teleport can connect to EMH power meters fitted with the Interface Module XC Modbus. You can connect using Modbus RTU using the RS485 serial interface.
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Interface Module XC Modbus.
-
Configure the Buad rate on the meter using the EMH COMBI-TOOL-Software.
- Navigate to the following menu: Meter —> Interfaces —> Electrical supplement / aditional interface
- Select a fixed baud rate
-
Teleport is configured to use the following default Modbus interface configuration of the module (let us know if you use a custom configuration):
- Device address:
1
- Baud rate:
9600
- Stop bits:
1
- Parity:
none
- Device address:
-
Configure the Modbus protocol, if that is not already done. All registers should be Holding registers with data type signed integer 32 and register length 2.
Modbus protocol
Register Address | Data Point | Unit |
---|---|---|
0 | Modbus ID-Address | - |
2 | Active Power Total | kW |
4 | Reactive Power Total | kvar |
6 | Apparent Power Total | kVA |
8 | Current L1 | A |
10 | Current L2 | A |
12 | Current L3 | A |
14 | Voltage L1 | V |
16 | Voltage L2 | V |
18 | Voltage L3 | V |
20 | Power factor | - |
22 | Frequency | Hz |
24 | Total Active Energy - Positive | kWh |
26 | Total Active Energy - Negative | kWh |