Solax Power
The Teleport can connect to Solax Power battery systems using Modbus RTU over RS485 or Modbus TCP. The asset can be directly controlled via the Teleport to manage the available mode of operation:
- Real Power Dispatch
Supported models
- TRENE
- AELIO
- ORI-P2500 / ORI-B5015L-2H (LC100)
ORI battery supported properties
Supported properties
activePowerreactivePowerbatteryStatusstateOfChargeavailableActivePower.chargeavailableActivePower.dischargeavailableEnergyfrequencypowerFactorstateOfHealthenergy.chargedenergy.dischargedbatteryEnergyStorageSystems[].stateOfChargebatteryEnergyStorageSystems[].availableEnergybatteryEnergyStorageSystems[].availableActivePower.chargebatteryEnergyStorageSystems[].availableActivePower.dischargebatteryEnergyStorageSystems[].roomTemperaturebatteryEnergyStorageSystems[].acVoltageLowVoltage.line.l1batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l2batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l3batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l1batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l2batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l3batteryEnergyStorageSystems[].racks[].dcVoltagebatteryEnergyStorageSystems[].racks[].dcCurrentbatteryEnergyStorageSystems[].racks[].cellTemperature.minbatteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMinbatteryEnergyStorageSystems[].racks[].cellTemperature.maxbatteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMaxbatteryEnergyStorageSystems[].racks[].cellVoltage.minbatteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMinbatteryEnergyStorageSystems[].racks[].cellVoltage.maxbatteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMaxbatteryEnergyStorageSystems[].racks[].cellVoltage.averagebatteryEnergyStorageSystems[].racks[].stateOfChargebatteryEnergyStorageSystems[].racks[].rackStatussetpoints.confirmed.activePowersetpoints.confirmed.chargeToPercentagesetpoints.confirmed.deliverFcrsetpoints.confirmed.reactivePower
Unsupported properties
availableReactivePower.injectavailableReactivePower.absorbratedEnergybatteryEnergyStorageSystems[].cellTemperature.minbatteryEnergyStorageSystems[].cellTemperature.maxbatteryEnergyStorageSystems[].acVoltageLowVoltage.phasebatteryEnergyStorageSystems[].acCurrentLowVoltage.lineactivePowerSetpoint.deliverFCRactivePowerSetpoint.chargeToStateactivePowerSetpoint.aggregate
Modbus TCP over Ethernet - configuration
-
Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.
-
Via the Solax Power’s web interface, go to EMS Settings > Network Settings, DHCP should be enabled and a reservation should be made in the router. Alternatively, DHCP can be disabled and an IP address set manually.
-
Go to System Management > Automation and disable all automations; These might interfere with the Teleport’s control logic.
-
Go to System Management > System Settings and disable control in the Export Settings and Impot Settings menus.
-
If a meter was previously connected to the battery but has been disconencted since, go to System Overview, select the meter, and click on the green box in the top-right corner that says “Maintenance” to turn off the “Communication loss shutdown enable”. Then, go to Device List and click the “Reset” button in the top-right corner.
-
Go to EMS Settings > Network Settings. Ensure LAN is selected as the “Communication Method” and that DHCP is enabled. The IP address is visible beneath. Provide this IP to Withthegrid.