The Teleport can connect to battery systems via the Sungrow Local Controller LC300, using Modbus TCP over Ethernet connection.

Setpoint operations

The asset can be controlled via the Teleport to set the following operations:

  • dispatchPower - to control active power setpoint, with 0.1kW resolution.

Supported & Unsupported properties

Supported properties
Supported properties:
  • activePower
  • reactivePower
  • powerFactor
  • frequency
  • availableEnergy
  • availableActivePower.charge
  • availableActivePower.discharge
  • stateOfCharge
  • stateOfHealth
  • batteryStatus
  • energy.charged
  • energy.discharged
  • ratedEnergy
  • batteryEnergyStorageSystems[].cellTemperature.min
  • batteryEnergyStorageSystems[].cellTemperature.max
  • batteryEnergyStorageSystems[].stateOfCharge
  • batteryEnergyStorageSystems[].racks[].stateOfCharge
  • batteryEnergyStorageSystems[].racks[].dcCurrent
  • batteryEnergyStorageSystems[].racks[].dcVoltage
  • batteryEnergyStorageSystems[].racks[].cellTemperature.max
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMax
  • batteryEnergyStorageSystems[].racks[].cellTemperature.min
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMin
  • batteryEnergyStorageSystems[].racks[].cellVoltage.max
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMax
  • batteryEnergyStorageSystems[].racks[].cellVoltage.min
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMin
  • batteryEnergyStorageSystems[].racks[].cellVoltage.average
Unsupported properties:
  • availableReactivePower.inject
  • availableReactivePower.absorb
  • batteryEnergyStorageSystems[].roomTemperature
  • batteryEnergyStorageSystems[].availableEnergy

Modbus TCP over ethernet

The Teleport can connect to the LC300 using Modbus TCP over Ethernet connection.

  1. Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.

  2. The LC300 has the following default Ethernet settings:

    • IP address: 192.168.1.100;
    • Subnet mask: 255.255.255.0;
    • Gateway: 192.168.1.1;
    • Port number: 502;