The Teleport can connect to Delta DelTerra C energy storage systems using Modbus TCP over ethernet.

Teleport can manage the available mode of operation:

  • Real Power Dispatch

Supported & Unsupported properties details

Properties

Supported Properties

  • frequency
  • activePower
  • reactivePower
  • powerFactor
  • stateOfCharge
  • stateOfHealth
  • batteryStatus
  • energy.charged
  • energy.discharged
  • availableActivePower.charge
  • availableActivePower.discharge
  • acCurrentMediumVoltage.phase.l1
  • acCurrentMediumVoltage.phase.l2
  • acCurrentMediumVoltage.phase.l3
  • acVoltageMediumVoltage.phase.l1
  • acVoltageMediumVoltage.phase.l2
  • acVoltageMediumVoltage.phase.l3
  • acVoltageMediumVoltage.line.l1
  • acVoltageMediumVoltage.line.l2
  • acVoltageMediumVoltage.line.l3
  • batteryEnergyStorageSystems[].stateOfCharge
  • batteryEnergyStorageSystems[].cellTemperature.max
  • batteryEnergyStorageSystems[].cellTemperature.min
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l1
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l2
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l3
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l1
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l2
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l3
  • batteryEnergyStorageSystems[].racks[].dcVoltage
  • batteryEnergyStorageSystems[].racks[].dcCurrent
  • batteryEnergyStorageSystems[].racks[].cellVoltage.min
  • batteryEnergyStorageSystems[].racks[].cellVoltage.max
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMin
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMax
  • batteryEnergyStorageSystems[].racks[].cellTemperature.min
  • batteryEnergyStorageSystems[].racks[].cellTemperature.max
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMin
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMax

Unsupported Properties

  • ratedEnergy
  • availableEnergy
  • availableReactivePower.inject
  • availableReactivePower.absorb
  • acCurrentMediumVoltage.line
  • batteryEnergyStorageSystems[].roomTemperature
  • batteryEnergyStorageSystems[].availableEnergy
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.line
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.line
  • batteryEnergyStorageSystems[].racks[].stateOfCharge
  • batteryEnergyStorageSystems[].racks[].cellVoltage.average

Configuration

Modbus TCP over ethernet
  1. Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport.

  2. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.

  3. Default IP addresses: 192.168.1.43, port 502;