Hager
Teleport can connect to the Hager ECR300C series energy meters using Modbus RTU over the RS-485 serial interface. For additional information, please refer to the official documentation.
Supported models
- ECR300C — 3-phase CT meter, screw terminals, magnitude summation (WELMEC)
- ECR301C — Swiss market variant (no reactive energies on display)
- ECR302C — Vectorial summation (ARN) variant
Configuration
Modbus RTU over RS-485
-
Connect the RS-485 serial cable between the serial port of the Teleport and the RS-485 terminal block of the Hager meter. The terminal block is labelled −, +, and 0 (Data−, Data+, and Signal Ground respectively).
-
Configure the CT ratio on the meter via the front-panel display. Navigate using the three buttons (OK, SCROLL, ESCAPE):
- From the main page, press SCROLL to navigate to Configuration.
- Press OK to enter, then scroll to Meter type / CT settings.
- Set the CT primary (e.g. 400 for a 400/5 A CT) and CT secondary (1 or 5) to match your installed current transformers.
- Press OK to confirm each value.
-
Configure the Modbus communication parameters on the meter. Still within the Configuration menu, scroll through and set each parameter:
- Modbus address:
1 - Baud rate:
19200 - Parity:
None - Stop bit:
1
Press OK to confirm each value. Press ESCAPE to return to the main page.
- Modbus address: