Skip to content

Phono

The Teleport can connect to a Phono battery energy storage system (BESS) via Modbus TCP over Ethernet.

Supported & Unsupported properties details

Properties
Supported Properties
  • batteryStatus
  • energy.charged
  • energy.discharged
  • frequency
  • activePower
  • reactivePower
  • stateOfCharge
  • ratedEnergy
  • availableActivePower.charge
  • availableActivePower.discharge
  • batteryEnergyStorageSystems[].roomTemperature
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l1
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l2
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l3
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l1
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l2
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l3
  • batteryEnergyStorageSystems[].racks[].stateOfCharge
  • batteryEnergyStorageSystems[].racks[].dcVoltage
  • batteryEnergyStorageSystems[].racks[].dcCurrent
  • batteryEnergyStorageSystems[].racks[].cellVoltage.max
  • batteryEnergyStorageSystems[].racks[].cellVoltage.min
  • batteryEnergyStorageSystems[].racks[].cellVoltage.average
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMax
  • batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMin
  • batteryEnergyStorageSystems[].racks[].cellTemperature.max
  • batteryEnergyStorageSystems[].racks[].cellTemperature.min
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMax
  • batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMin

Unsupported Properties
  • stateOfHealth
  • availableEnergy
  • availableReactivePower.inject
  • availableReactivePower.absorb
  • batteryEnergyStorageSystems[].stateOfCharge
  • batteryEnergyStorageSystems[].availableEnergy
  • batteryEnergyStorageSystems[].cellTemperature
  • batteryEnergyStorageSystems[].availableActivePower.charge
  • batteryEnergyStorageSystems[].availableActivePower.discharge
  • batteryEnergyStorageSystems[].acVoltageLowVoltage.phase
  • batteryEnergyStorageSystems[].acCurrentLowVoltage.line
Setpoint operations

The asset can be controlled via the Teleport to set the following operation.

  • dispatchPower - to control the active power setpoint.

The active power setpoint resolution is 0.1 kW. The EMS is automatically switched to Remote operating mode before writing the active power setpoint.

Configuration

Modbus TCP over Ethernet
  1. Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport.

  2. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.

  3. Configure the Phono Modbus TCP connection using the IP address and port provided by the Phono system.