Skip to content

Flexecharge

The Teleport can connect to the Flexecharge EV EMS using Modbus TCP via port 502 of the Flexecharge GATEWAY.

Current firmware

The Teleport writes an absolute active power setpoint in watts to the GATEWAY, and reads back the applied limit and the active power. The GATEWAY uses this setpoint as the DSO control limit in its load management.

Registers

The Teleport expects the following registers. All registers are holding registers, use big endian byte order and unit identifier 255. The registers must be configured in HARMON-E, see below.

Register name in HARMON-ERegister addressData type
Active power absolute setpoint0UInt32
Active power instantaneous100UInt32
Active power absolute feedback102UInt32

Configuration in HARMON-E

Ask Flexecharge Support to enable DSO Control via Modbus on the GATEWAY before you start. Make sure the power meter for grid control is configured on the Power meters page.

  1. Open the site in HARMON-E and select Grid control in the Application menu.

  2. Under Actions, select Standard configuration and switch on Enable Grid control.

  3. Configure the general settings:

    • Power meter: the power meter assigned to grid control
    • Control interface: Modbus
    • Endian: big
  4. Under Register configuration, add one entry per register from the table above, and select Save.

  5. Share the GATEWAY IP address with the withthegrid team. You can find it in the Control Hub: the IP address in the OCPP URL, for example ws://192.168.77.2.

Legacy firmware

Older Flexecharge GATEWAY firmware versions use a legacy Modbus interface that differs from the current implementation in the following ways:

  • Current-based setpoints: The Teleport writes a charging current limit in amperes (A) rather than an active power limit in watts (W).
  • No feedback or meter telemetry: The legacy interface does not expose registers for reading back the applied setpoint or instantaneous power meter measurements. Because no telemetry is read back, the Teleport operates in open-loop control and cannot verify actual power consumption or setpoint compliance.