Xemex

Teleport can connect to the Xemex Smart Connect using Modbus TCP over Ethernet. The Smart Connect reads the P1/A1 port of a smart meter.

Supported models
  • Smart Connect P1/A1
Supported properties
  • voltage.phase.l1 (4-wire)
  • voltage.phase.l2 (4-wire)
  • voltage.phase.l3 (4-wire)
  • voltage.line.l1 (3-wire)
  • voltage.line.l2 (3-wire)
  • voltage.line.l3 (3-wire)
  • current.l1
  • current.l2
  • current.l3
  • activePower.l1
  • activePower.l2
  • activePower.l3
  • activePower.sum
  • reactivePower.l1
  • reactivePower.l2
  • reactivePower.l3
  • reactivePower.sum
  • apparentPower.l1
  • apparentPower.l2
  • apparentPower.l3
  • apparentPower.sum
  • powerFactor.l1
  • powerFactor.l2
  • powerFactor.l3
  • activeEnergyConsumed.sum
  • activeEnergyDelivered.sum

Modbus TCP over Ethernet

  1. Connect the Ethernet cable between the ETH1 port of the Teleport and the router. Navigate to our appendix for generic instructions on how to integrate with a router.

  2. Connect the Smart Connect to the P1/A1 port of the meter and power it using its USB-C supply.

  3. Connect the Ethernet cable between the router and the Smart Connect. The Smart Connect requests an IP address via DHCP by default. Configure the router to assign a fixed IP to the Smart Connect, or set a static IP in its web interface at http://smart-connect.

  4. Inform us of:

    • The IP address of the Smart Connect. The Teleport connects on the default Modbus TCP port 502; a device address (i.e. Slave ID/ Unit ID) does not need to be configured.
    • Whether the meter is connected 3-wire or 4-wire.
    • The current and voltage transformer ratios, if applicable (e.g. 200/5 A and 10 kV/100 V).