Gotion
The Teleport can connect to Gotion battery systems using Modbus TCP over ethernet (recommended) or Modbus RTU over RS485. The battery system can be directly controlled via Teleport to manage the available mode of operation:
Supported models
- ESC-R100-211-CE
The battery system can be directly controlled via Teleport to manage the available mode of operation:
- Real Power Dispatch
Supported properties
Supported properties
energy.charged
energy.discharged
frequency
activePower
reactivePower
stateOfCharge
stateOfHealth
powerFactor
batteryStatus
availableActivePower.charge
availableActivePower.discharge
acVoltageMediumVoltage.phase.l1
acVoltageMediumVoltage.phase.l2
acVoltageMediumVoltage.phase.l3
acCurrentMediumVoltage.phase.l1
acCurrentMediumVoltage.phase.l2
acCurrentMediumVoltage.phase.l3
batteryEnergyStorageSystems[].identifier
batteryEnergyStorageSystems[].cellTemperature.min
batteryEnergyStorageSystems[].cellTemperature.max
batteryEnergyStorageSystems[].stateOfCharge
batteryEnergyStorageSystems[].racks[]
batteryEnergyStorageSystems[].racks[].identifier
batteryEnergyStorageSystems[].racks[].stateOfCharge
batteryEnergyStorageSystems[].racks[].cellTemperature.min
batteryEnergyStorageSystems[].racks[].cellTemperature.max
batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMin
batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMax
batteryEnergyStorageSystems[].racks[].cellVoltage.min
batteryEnergyStorageSystems[].racks[].cellVoltage.max
batteryEnergyStorageSystems[].racks[].cellVoltage.average
batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMin
batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMax
batteryEnergyStorageSystems[].racks[].dcCurrent
batteryEnergyStorageSystems[].racks[].dcVoltage
Unsupported properties
availableEnergy
availableReactivePower.inject
availableReactivePower.absorb
ratedEnergy
acVoltageMediumVoltage.line.l1
acVoltageMediumVoltage.line.l2
acVoltageMediumVoltage.line.l3
acCurrentMediumVoltage.line
batteryEnergyStorageSystems[].roomTemperature
batteryEnergyStorageSystems[].availableEnergy
Configuration
In order to enable control over Modbus you have to configure the following settings on the battery. Go to Configurate - Basic settings:
- Networking mode: Slave
- Load following: Disable
- Control mode: Remote control
Modbus TCP over Ethernet (recommended)
Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.
Modbus RTU over RS485
- Connect the serial cable between the serial port of the Teleport and the serial port of the battery.
- The default settings from the battery manual can be found below. Please let us know if you configure the battery with different settings:
- Device address:
1
- Baud rate:
9600
- Stop bits:
1
- Start bits:
1
- Data bits:
8
- Parity:
None
- Device address: