Wolong-ATB
The Teleport can connect to Wolong-ATB Battery systems using Modbus RTU over RS485. The asset can be directly controlled via the Teleport to manage the available mode of operation:
- Real Power Dispatch
Supported models
- WL-ESS-1543kW3086kWh-0.69kV
- WL-ESS-110kW235kWh-0.4kV
Configuration
Modbus TCP over ethernet
Connection via a router (recommended)
- Connect the ethernet cable between the ETH1 port of the Teleport and the router. Navigate to our appendix for generic instructions on how to integrate with a router. Make sure to note the IP of Teleport and the IP of the asset(s). The router should be configured to assign a fixed IP to the meter.
Direct connection via the LAN port of the meter
-
Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the Wolong/ATB Battery.
-
Configure the following settings, with values as described in Static IPs for a direct asset connection.
- IP address
- IP mask
- Device Address:
1
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the battery.
-
Check that the settings are configured to the default values:
- Device address:
1
- Baud rate:
9600
- Stop bits:
1
- Start bits:
1
- Parity:
None
- Device address: