Chint
Teleport can connect to Chint meters. You can connect using Modbus RTU using the RS485 serial interface.
Supported models
- DTSU666
- DSSU666
Modbus RTU over RS485
- Connect the serial cable between the serial port of the Teleport and the serial port of the meter. The RS-485 connection between the Chint meter and Teleport is shown in the table below.
Chint meter Teleport 24 (A) D+
25 (B) D-
- Teleport is configured to use the following Modbus interface configuration. Please configure the meter to use the same settings or let us know if you use a custom configuration:
- Device address:
1
- Baud rate:
9600
- Stop bits:
1
- Parity:
none
- Device address: