Schneider Electric
Teleport can connect to a number of Schneider Electric metering products. You can connect using Modbus TCP over ethernet (recommended) or Modbus RTU using the RS485 serial interface. For additional information, please refer to the manufacturer user manual.
Supported models
- PM3250
- PM3255
- PM5110
- PM5310
- PM5320
- PM5330
- PM5340
- PM5560
- PM5563
- PM5563RD
- PM710
- PM750
- PM8000 series
- iEM3000 series
- iEM3150
- iEM3155
- iEM3250
- iEM3255
- iEM3350
- iEM3355
- iEM3455
- iEM3555
Configuration
Modbus TCP over ethernet
The Teleport can be connected to the Schneider Electric meter via a router or directly via the LAN port of the meter. PM5320, PM5340 and PM5500 meters do not currently support DHCP with a router, so a direct connection between the meter and the Teleport is necessary.
Connection via a router (recommended)
This is only possible for the PM8000 series with ION Setup
-
Connect the ethernet cable between the ETH1 port of the Teleport and the router. Navigate to our appendix for generic instructions on how to integrate with a router. Make sure to note the IP of Teleport and the IP of the asset(s).
-
Start the ION setup and navigate to Startup Assistant > Communications > Basic Ethernet > IPv4.
-
Select the IP address and click
Edit
, then select DHCP as the preferred IP address assignment mode. -
Click
OK
to finalize the setting.
Direct connection via the LAN port of the Schneider Electric meter
PM5320, PM5340 and PM5500 series
-
Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the Schneider Electric asset.
-
Access the meter webpages via the meter IP address and log in. Navigate to Settings > Modbus TCP/IP filtering or Settings > Communication > IP filtering depending on your firmware version. Configure the following settings, with values as described in Static IPs for a direct asset connection.
- IP Address
- Subnet Mask
- Gateway
PM8000 series
-
Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the Schneider Electric asset.
-
Start the ION setup and navigate to Startup Assistant > Communications > Basic Ethernet > IPv4.
-
Select the IP address and click
Edit
, then select Stored as the preferred IP address assignment mode. -
In the IP settings, configure the following parameters, with values as described in Static IPs for a direct asset connection.
- IP Address
- Subnet Mask
- Gateway
Modbus RTU over RS485
PM8000
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Schneider Electric asset.
-
Navigate to Home > Setup Menu > Communications Setup > Com1 Setup and input the following settings
- Protocol:
Modbus RTU
- Baud rate:
19200
- Rx Timeout:
0.1
- Unit ID:
100
- Serial Port:
8N2
- RS485 Bias:
ON
- Protocol:
Other models
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Schneider Electric asset.
-
Confirm the following settings in the Schneider Electric asset:
- Baud rate:
19200
- Parity:
None
- Device address:
1
- Baud rate: