INVT
The Teleport can connect to all INVT on-grid and off-grid solar inverters. You can connect with Modbus RTU using RS485 serial interface.
Supported properties
generatedEnergyactivePoweractivePowerLimit.percentage
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the INVT inverter.
-
On the inverter’s LCD display, go to Settings, follow the inverter’s user manual to enter the password: 123, and then navigate to COM Address. In the case of a single inverter, verify the COM Address is
1. In the case of multiple inverters, please set each inverter to a different address and let us know these addresses.
The default Modbus RTU settings are:
- Baud rate:
9600 - Parity bit:
none - Data bit:
8 - Stop bit:
1