SMA
Supported models
- SMA Data Manager L
- SMA Data Manager M
- SMA Data Manager M Lite
- SMA Inverter Manager
- SMA Cluster Controller
- Sunny Tripower 60
- Sunny Tripower CORE1
- Sunny Tripower X 12 / 15 / 20 / 25
- Sunny Tripower CORE2
- Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (firmware version 3.10.10.R)
- Sunny Tripower 8.0–10.0 (firmware version 3.10.08.R – HP1 and HP2)
- Sunny Tripower Smart Energy 5.0 / 6.0 / 8.0 / 10.0 (firmware version 3.00.02.R)
- Sunny Boy 1.5 / 2.0 / 2.5 (firmware version 3.10.07.R)
- Sunny Boy 3.0 / 3.6 / 4.0 / 5.0 / 6.0
- Sunny Boy 5.5-JP (firmware version 1.02.06.R)
- Sunny Boy Storage 3.7 / 5.0 / 6.0 (firmware version 3.12.33.R)
- Sunny Boy Storage 2.5 (firmware version 3.11.12.R)
- Sunny Highpower PEAK3 (firmware version 3.11.33.R)
- Sunny Tripower 15000TL (only in combination with a Data Manager)
- Sunny Tripower 20000TL (only in combination with a Data Manager)
- Sunny Tripower 25000TL (only in combination with a Data Manager)
SMA Configuration
Configuration with the user interface of a SMA data manager
-
Access the Web UI of the data manager with its IP address.
-
Log into the user interface.
-
On the top bar, click Select Device and select the data manager from the drop-down menu.
-
On the left sidebar, go to Configuration - External communication.
-
Under Modbus server, click Carry out initial configuration.
-
Check the box at Enable Modbus server.
-
Validate that the Port is
502
. -
On the top bar, click the Home icon
-
In the left sidebar, go to Configuration - Grid management service
-
Choose Configuration & activation for Active Power. In the wizard that is displayed:
-
ensure total system power is correct
-
- select “Open loop control”
- leave all “Signal sources” unchecked
- enable “Direct selling interface” and select “Standard modbus interface”
-
- enter 1 at “Setting time”
- enter 100 at “Active power gradient”
- press Save
-
-
In the left sidebar, go to Configuration - Parameter
-
Under Filter, enter
External active power
-
Verify that:
External active power setpoint via Modbus (direct seller)
isOn
External active power setpoint via Modbus (electric utility company)
isOff
External active power setpoint
isOn
External active power setpoint 2
isOff
-
If you had to make changes in the previous step, press Save at the bottom
Optional extra steps for fallback configuration
-
In the left sidebar, go to Configuration - Parameter and:
- Change External active power setting, fallback behavior to
Apply fallback values
. - Change External active power setting, fallback value of maximum active power to
0
or other max fallback limit. - Change External active power setting, fallback value of minimum active power to
0
or other min fallback limit. - Change External active power setting, timeout to
60
.
- Change External active power setting, fallback behavior to
Configuration with the user interface of an SMA inverter or inverter manager
-
Establish a connection to the user interface (see the inverter / inverter manager manual).
-
Log into the user interface as an Installer (access the login page via the inverter / inverter manager’s IP address).
-
Select the Device Parameters tab.
-
Select Edit parameters.
-
Select the parameter group External Communication.
-
To activate the TCP server, make the following settings in the group Modbus > TCP Server:
- In the drop-down list Activated, select the entry Yes.
- Verify the Port is set to 502.
-
Select the parameter group System and device control.
-
Ensure that WModCfg.WMod is set to External active power setpoint.
-
Select Save all.
Configuration with Sunny Explorer
-
Start Sunny Explorer on the computer and create Speedwire plant (see Sunny Explorer user manual).
-
Log into the Speedwire system as Installer.
-
Select the SMA inverter to be configured in the system directory.
-
Select the tab Settings.
-
Select the parameter group External Communication.
-
Select Edit.
-
To activate the TCP server, make the following settings in the group Modbus > TCP Server:
- In the drop-down list Activated, select the entry Yes.
- Verify the Port is set to 502.
-
Select the parameter group System and device control.
-
Ensure that WModCfg.WMod is set to External active power setpoint.
-
Select Save all.
Modbus TCP over ethernet
Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the SMA asset. If the LAN port of the asset is already occupied (e.g. connected to a router), navigate to our appendix for instructions on how to integrate with a router. The Modbus TCP over ethernet (Speedwire) settings can be configured similarly to enabling Modbus TCP.
-
From Device Parameters/Settings, depending on which configuration type you have followed, navigate to System communication.
-
Select Edit and configure the following settings, with values as described in Static IPs for a direct asset connection.
- IP Address
- Subnet Mask
- Gateway:
0.0.0.0
or192.168.0.11
if you want to use e.g. Sunny Portal - DNS server IP
-
If you are connecting multiple assets, follow the same instructions with a different IP address.