ABB
Teleport can connect to several ABB power meters. You can connect to A43, A44, B23 and B24 meters using Modbus RTU using the RS485 serial interface. M4M 20 and M4M 30 meters support Modbus RTU over RS485 or Modbus TCP over Ethernet, depending on the specific model. More configuration information for e.g. the A43 series can be found in the official documentation.
Supported models
- A43
- A44
- B23
- B24
- M4M 20
- M4M 30
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the meter.
-
Set the communication to RS485:
- Select
SET
and pressOK
- Select
RS-485
and pressOK
- Select
Protoc
and pressOK
to see the selected protocol. If this is not configured toModbus
, select it and pressOK
. Press and holdOK
to step back into the previous menu - Press
↓
to see the baud rate, modbus device address and parity and change these to the desired values
- Select
-
Teleport is configured to use the following default Modbus interface configuration of the meter (let us know if you use a custom configuration):
- Device address:
1
- Baud rate:
19200
- Stop bits:
2
- Parity:
none
- Device address:
Modbus TCP over ethernet (M4M series only)
-
Connect the ethernet cable between the ETH1 port of the Teleport and the router. Navigate to our appendix for generic instructions on how to integrate with a router. Make sure to note the IP of Teleport and the IP of the asset(s). The router should be configured to assign a fixed IP to the meter.
-
Connect the ethernet cable between the router and the ABB meter.
-
Inform us of the chosen IP and port settings.