Fronius Smart Meter

Teleport can read out Fronius Smart Meters through the Fronius Datamanager. The Smart Meter must be connected to the Fronius Datamanager via Modbus RTU over RS485, while the Teleport is connected to the Datamanager using Modbus TCP over ethernet. More configuration information can be found in the official documentation.

Supported models
  • Smart Meter TS 5ka-3
  • Smart Meter TS 63A-3
  • Smart Meter TS 100A-1
  • Smart Meter 50kA-3
  • Smart Meter 63A-1
  • Smart Meter 63A-3
  • Smart Meter IP
  • Smart Meter WR

Configuration

Modbus TCP over ethernet

  1. Connect the ethernet cable between the ETH1 port of the Teleport and the router. Navigate to our appendix for generic instructions on how to integrate with a router. Make sure to note the IP of Teleport and the IP of the asset(s). The router should be configured to assign a fixed IP to the meter.

  2. Connect the ethernet cable between the router and the Fronius Datamanager.

  3. Modbus Settings: navigate to the Datamanager web interface following asset instructions and go to Settings > Modbus. (For the Datamanager 2.0, go to Communication > Modbus)

    • Data export via Modbus: tcp
    • Modbus port: 502
    • Sunspec Model Type: float
    • IP Address: 192.168.1.1

Direct connection via the LAN port of the Datamanager

  1. Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the Fronius Datamanager.

  2. Connect the ethernet cable between the router and the Fronius Datamanager.

  3. Modbus Settings: navigate to the Datamanager web interface following asset instructions and go to Settings > Modbus. (For the Datamanager 2.0, go to Communication > Modbus) Configure the following settings, with the IP as described in Static IPs for a direct asset connection.

    • Data export via Modbus: tcp
    • Modbus port: 502
    • Sunspec Model Type: float
    • IP Address