OX Power
The Teleport can connect to Gotion battery systems using Modbus RTU over RS485. The battery system can be directly controlled via Teleport to manage the available mode of operation:
- Real Power Dispatch
Supported properties
Supported:
frequency
activePower
reactivePower
stateOfCharge
stateOfHealth
batteryStatus
acCurrentMediumVoltage.phase.l1
acCurrentMediumVoltage.phase.l2
acCurrentMediumVoltage.phase.l3
acVoltageMediumVoltage.phase.l1
acVoltageMediumVoltage.phase.l2
acVoltageMediumVoltage.phase.l3
batteryEnergyStorageSystems[].racks[].dcVoltage
batteryEnergyStorageSystems[].racks[].dcCurrent
Unsupported:
powerFactor
availableEnergy
availableActivePower.charge
availableActivePower.discharge
energy.charged
energy.discharged
ratedEnergy
availableReactivePower.inject
availableReactivePower.absorb
batteryEnergyStorageSystems[].stateOfCharge
batteryEnergyStorageSystems[].availableEnergy
batteryEnergyStorageSystems[].roomTemperature
batteryEnergyStorageSystems[].cellTemperature.min
batteryEnergyStorageSystems[].cellTemperature.max
Configuration
Modbus RTU over RS485
- Connect the serial cable between the serial port of the Teleport and the serial port of the battery.
- The default settings from the battery manual can be found below. Please let us know if you configure the battery with different settings:
- Device address:
1
- Baud rate:
9600
- Stop bits:
1
- Parity:
None
- Device address: