OX Power
The Teleport can connect to Gotion battery systems using Modbus RTU over RS485. The battery system can be directly controlled via Teleport to manage the available mode of operation:
- Real Power Dispatch
Supported properties
Supported:
frequencyactivePowerreactivePowerstateOfChargestateOfHealthbatteryStatusacCurrentMediumVoltage.phase.l1acCurrentMediumVoltage.phase.l2acCurrentMediumVoltage.phase.l3acVoltageMediumVoltage.phase.l1acVoltageMediumVoltage.phase.l2acVoltageMediumVoltage.phase.l3batteryEnergyStorageSystems[].racks[].dcVoltagebatteryEnergyStorageSystems[].racks[].dcCurrent
Unsupported:
powerFactoravailableEnergyavailableActivePower.chargeavailableActivePower.dischargeenergy.chargedenergy.dischargedratedEnergyavailableReactivePower.injectavailableReactivePower.absorbbatteryEnergyStorageSystems[].stateOfChargebatteryEnergyStorageSystems[].availableEnergybatteryEnergyStorageSystems[].roomTemperaturebatteryEnergyStorageSystems[].cellTemperature.minbatteryEnergyStorageSystems[].cellTemperature.max
Configuration
Modbus RTU over RS485
- Connect the serial cable between the serial port of the Teleport and the serial port of the battery.
- The default settings from the battery manual can be found below. Please let us know if you configure the battery with different settings:
- Device address:
1 - Baud rate:
9600 - Stop bits:
1 - Parity:
None
- Device address: