Solax Power
The Teleport can connect to the Solax inverters included in the list of supported models below. You can connect with Modbus RTU using RS485 serial interface.
Supported models
X3-MIC G2A1-Hybrid-6.0-USA1-Hybrid-7.0-USA1-Hybrid-7.6-USA1-Hybrid-8.6-USA1-Fit-6.0-USA1-Fit-7.0-USA1-Fit-7.6-USA1-Fit-8.6-USA1-6.0-USA1-7.0-USA1-7.6-USA1-8.6-USX3-FORTHX3-MEGA
Supported properties
generatedEnergyactivePoweractivePowerLimit.percentageinverters[].activePowerinverters[].generatedEnergy
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Solax inverter.
-
On the inverter’s LCD display, go to Settings, follow the inverter’s user manual to enter the password, and then navigate to RS485 CommAddr. In the case of a single inverter, verify the COM Address is
1. In the case of multiple inverters, please set each inverter to a different address and let us know these addresses. -
Navigate to Modbus Function and set it to
COM485. -
Navigate to ParallelSetting and set it to
Disable.