Dyness
The Teleport can connect to the Dyness products included in the list of supported models below.
Supported models
- DH200F
Soon to be implemented:
- DH200Y
- DH100F
Supported & Unsupported properties details
Properties
Supported properties
frequency
activePower
reactivePower
powerFactor
availableActivePower.charge
availableActivePower.discharge
stateOfCharge
stateOfHealth
batteryStatus
acCurrentMediumVoltage.phase.l1
acCurrentMediumVoltage.phase.l2
acCurrentMediumVoltage.phase.l3
acVoltageMediumVoltage.line.l1
acVoltageMediumVoltage.line.l2
acVoltageMediumVoltage.line.l3
acVoltageMediumVoltage.phase.l1
acVoltageMediumVoltage.phase.l2
acVoltageMediumVoltage.phase.l3
batteryEnergyStorageSystems[]
batteryEnergyStorageSystems[].cellTemperature.min
batteryEnergyStorageSystems[].cellTemperature.max
batteryEnergyStorageSystems[].roomTemperature
batteryEnergyStorageSystems[].racks[]
batteryEnergyStorageSystems[].racks[].dcVoltage
batteryEnergyStorageSystems[].racks[].dcCurrent
Unsupported properties
availableEnergy
energy.charged
energy.discharged
ratedEnergy
availableReactivePower.inject
availableReactivePower.absorb
batteryEnergyStorageSystems[].stateOfCharge
batteryEnergyStorageSystems[].availableEnergy
batteryEnergyStorageSystems[].availableActivePower.charge
batteryEnergyStorageSystems[].availableActivePower.discharge
Setpoint operations
The asset can be controlled via the Teleport to set the following operations.
dispatchPower
- to control active power setpoint
Modbus configuration
The Teleport can connect to Dyness battery systems using Modbus RTU over RS485 or TCP over Ethernet connection.
Modbus TCP over ethernet
-
Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.
-
Go to Setting > EMS > SysSet > Network to configure the TCP network configuration.
-
Refer to the Dyness EMS Quick Adaptation Manual - modbus protocol or similar, for more TCP configuration instructions.
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Dyness battery.
-
Check that the default settings are:
- Device address:
1
- Data bits:
8
- Stop bits:
1
- Parity:
None
- Baud rate:
115200 bps
- Device address:
-
Refer to the Dyness EMS Quick Adaptation Manual - modbus protocol or similar, for more configuration instructions.