Dyness
The Teleport can connect to the Dyness products included in the list of supported models below.
Supported models
- DH200F
Soon to be implemented:
- DH200Y
- DH100F
Supported & Unsupported properties details
Properties
Supported properties
frequencyactivePowerreactivePowerpowerFactoravailableActivePower.chargeavailableActivePower.dischargestateOfChargestateOfHealthbatteryStatusacCurrentMediumVoltage.phase.l1acCurrentMediumVoltage.phase.l2acCurrentMediumVoltage.phase.l3acVoltageMediumVoltage.line.l1acVoltageMediumVoltage.line.l2acVoltageMediumVoltage.line.l3acVoltageMediumVoltage.phase.l1acVoltageMediumVoltage.phase.l2acVoltageMediumVoltage.phase.l3batteryEnergyStorageSystems[]batteryEnergyStorageSystems[].cellTemperature.minbatteryEnergyStorageSystems[].cellTemperature.maxbatteryEnergyStorageSystems[].roomTemperaturebatteryEnergyStorageSystems[].racks[]batteryEnergyStorageSystems[].racks[].dcVoltagebatteryEnergyStorageSystems[].racks[].dcCurrent
Unsupported properties
availableEnergyenergy.chargedenergy.dischargedratedEnergyavailableReactivePower.injectavailableReactivePower.absorbbatteryEnergyStorageSystems[].stateOfChargebatteryEnergyStorageSystems[].availableEnergybatteryEnergyStorageSystems[].availableActivePower.chargebatteryEnergyStorageSystems[].availableActivePower.discharge
Setpoint operations
The asset can be controlled via the Teleport to set the following operations.
dispatchPower- to control active power setpoint
Modbus configuration
The Teleport can connect to Dyness battery systems using Modbus RTU over RS485 or TCP over Ethernet connection.
Modbus TCP over ethernet
-
Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.
-
Go to Setting > EMS > SysSet > Network to configure the TCP network configuration.
-
Refer to the Dyness EMS Quick Adaptation Manual - modbus protocol or similar, for more TCP configuration instructions.
Modbus RTU over RS485
-
Connect the serial cable between the serial port of the Teleport and the serial port of the Dyness battery.
-
Check that the default settings are:
- Device address:
1 - Data bits:
8 - Stop bits:
1 - Parity:
None - Baud rate:
115200 bps
- Device address:
-
Refer to the Dyness EMS Quick Adaptation Manual - modbus protocol or similar, for more configuration instructions.