Sinexcel 500KTL

The Teleport can connect to a battery systems composed by the inverters Sinexcel 500KTL, connected to the SparQ BESS, via Modbus TCP over ethernet.

Supported models:
  • Inverters PWS1-500KTL from Sinexcel - standard without STS.

Supported & Unsupported properties details

Properties
Supported Properties
  • frequency
  • activePower
  • powerFactor
  • reactivePower
  • availableActivePower.charge
  • availableActivePower.discharge
  • stateOfCharge
  • stateOfHealth
  • batteryStatus
  • energy.charged
  • energy.discharged
  • acCurrentMediumVoltage.phase.l1
  • acCurrentMediumVoltage.phase.l2
  • acCurrentMediumVoltage.phase.l3
  • acVoltageMediumVoltage.line.l1
  • acVoltageMediumVoltage.line.l2
  • acVoltageMediumVoltage.line.l3
  • batteryEnergyStorageSystems[].cellTemperature.max
  • batteryEnergyStorageSystems[].cellTemperature.min
  • batteryEnergyStorageSystems[].stateOfCharge
  • setpoints.confirmed.activePower

Unsupported Properties
  • availableEnergy
  • ratedEnergy
  • availableReactivePower.inject
  • availableReactivePower.absorb
  • acCurrentMediumVoltage.line
  • acVoltageMediumVoltage.phase.l1
  • acVoltageMediumVoltage.phase.l2
  • acVoltageMediumVoltage.phase.l3
  • batteryEnergyStorageSystems[].roomTemperature
  • batteryEnergyStorageSystems[].availableEnergy
  • batteryEnergyStorageSystems[].racks[]
  • setpoints.confirmed.chargeToPercentage
  • setpoints.confirmed.deliverFcr
  • setpoints.confirmed.reactivePower
Setpoint operations

The asset can be controlled via the Teleport to set the following operations.

  • dispatchPower - to control active power setpoint

The active power setpoint resolution is 0.1 kW.

Configuration

Modbus TCP over ethernet

This integration handles two distinct devices: the BMS (SparQ) and the PCS (Sinexcel-500ktl) which controls the BMS. Each device requires its own IP address.

  1. Connect an Ethernet cable between the asset and either a router or an Ethernet port of the Teleport. If connected via a router, please navigate to our appendix for more instructions on how to integrate with a router.

  2. On the inverter’s physical interface, select the tab Ctrl mode and activate Remote mode.

Default IP addresses:

  • BMS: 10.30.4.13, port 503;
  • PCS: 192.168.1.10;

It is possible to configure specific slave IDs for each asset. Default slave ID used for both is 1.