Skip to content

Eastron

Teleport can connect to Eastron meters. You can connect using Modbus RTU using the RS485 serial interface. More configuration information can be found in the official documentation.

Supported models
  • SDM630
  • SDM630-EV
  • SDM630MCT
  • SMART X96

Modbus RTU over RS485

  1. Connect the serial cable between the serial port of the Teleport and the serial port of the meter.

  2. On the Eastron meter, go to the communication menu: - Set the modbus device address, baud rate, and parity and change these to the desired values.

  3. Teleport is configured to use the following default Modbus interface configuration of the meter:

    • Device address: 1
    • Baud rate: 19200
    • Stop bits: 1
    • Parity: none