Skip to content

Janitza

Teleport can connect to a number of Janitza products. You can connect using Modbus TCP over ethernet (recommended) or Modbus RTU using the RS485 serial interface. More configuration information can be found in the official documentation.

Supported models
  • UMG 508
  • UMG 509 PRO
  • UMG 512 PRO
  • UMG 604 PRO
  • UMG 605 PRO
  • UMG 801
  • UMG 806
  • UMG 96RM-E
  • UMG 96RM
  • UMG 96RM-P
  • UMG 96RM-PN
  • UMG 96RM-CMB
  • UMG 96-PQ-L
  • UMG 96-PA
  • UMG 96-PA-MID+
  • UMG 96-S2
  • UMG 103
  • UMG 103-CBM
  • RMU 301-CBM
  • MID energy meter and measurement system

Configuration

Modbus TCP over ethernet

  1. Connect the ethernet cable between the ETH1 port of the Teleport and the LAN port of the Janitza Ethernet communication module. If the LAN port of the module is already occupied (e.g. connected to a router), navigate to our appendix for instructions on how to integrate with a router.

  2. In case Teleport connects directly to the meter, navigate to Settings and TCP/IP. Configure the following settings, with values as described in Static IPs for a direct asset connection.

    • DHCP: OFF
    • IP Address
    • Subnet Mask
    • Gateway
  3. Navigate to Settings and Modbus and validate following settings related to Modbus:

    • Device address: 1
    • Mode: Slave
    • Device address EC1: 2

Let us know your device address in case you require a value different from the suggested one.