PeerGen
The Teleport can connect to the PeerGen Battery Energy Storage System (BESS) through the LC cabinet. Teleport can manage the following mode(s) of operation:
- Real Power Dispatch
Supported properties
Supported:
frequency
activePower
reactivePower
powerFactor
availableEnergy
stateOfCharge
batteryStatus
acCurrentMediumVoltage.phase.l1
acCurrentMediumVoltage.phase.l2
acCurrentMediumVoltage.phase.l3
acVoltageMediumVoltage.line.l1
acVoltageMediumVoltage.line.l2
acVoltageMediumVoltage.line.l3
acVoltageMediumVoltage.phase.l1
acVoltageMediumVoltage.phase.l2
acVoltageMediumVoltage.phase.l3
batteryEnergyStorageSystems[].stateOfCharge
batteryEnergyStorageSystems[].availableEnergy
batteryEnergyStorageSystems[].cellTemperature.min
batteryEnergyStorageSystems[].cellTemperature.max
batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l1
batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l2
batteryEnergyStorageSystems[].acVoltageLowVoltage.line.l3
batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l1
batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l2
batteryEnergyStorageSystems[].acVoltageLowVoltage.phase.l3
batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l1
batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l2
batteryEnergyStorageSystems[].acCurrentLowVoltage.phase.l3
batteryEnergyStorageSystems[].roomTemperature
batteryEnergyStorageSystems[].racks[].stateOfCharge
batteryEnergyStorageSystems[].racks[].dcCurrent
batteryEnergyStorageSystems[].racks[].dcVoltage
batteryEnergyStorageSystems[].racks[].cellTemperature.min
batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMin
batteryEnergyStorageSystems[].racks[].cellTemperature.max
batteryEnergyStorageSystems[].racks[].cellTemperature.cellIdMax
batteryEnergyStorageSystems[].racks[].cellVoltage.min
batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMin
batteryEnergyStorageSystems[].racks[].cellVoltage.max
batteryEnergyStorageSystems[].racks[].cellVoltage.cellIdMax
batteryEnergyStorageSystems[].racks[].cellVoltage.average
Unsupported:
availableActivePower.charge
availableActivePower.discharge
energy.charged
energy.discharged
stateOfHealth
ratedEnergy
acCurrentMediumVoltage.line
availableReactivePower.inject
availableReactivePower.absorb
batteryEnergyStorageSystems[].acCurrentLowVoltage.line
batteryEnergyStorageSystems[].racks[].rackStatus
Configuration
Modbus TCP
-
Connect the ethernet cable between the ETH1 port of the Teleport and the Ethernet port of the battery. If this port is already connected to the router, navigate to our appendix for generic instructions on how to integrate with a router. Make sure to note the IP of Teleport and the IP of the asset(s).
-
The default settings for the Peergen battery system are:
- IP address:
192.168.1.101
- Port:
502
- IP address: