Skip to content

  • Added setpoints object
[
{
"type": "batteryPower.flash:1", // identifies this schema
"teleportHashId": "8de4y2", // uniquely identifies the teleport device
"assetIdentifier": "alfen-123", // globally unique identifier of the asset, when available the brand and serial number of the asset
"attempt": 0, // 0-indexed delivery attempt. integer
"isDeferred": false, // chronological ordering (by asset identifier) is only guaranteed for messages with isDeferred: false.
"measuredAt": "2023-01-01T00:00:00Z", // when read-out started, ISO 8601 yyyy-mm-ddThh:mm:ssZ or YYYYYY-MM-DDTHH:mm:ss.sssZ, so in UTC
"frequency": 50.1, // in Hz, can be null
"activePower": 1000.1, // in W, can be null. Positive means discharging, negative charging.
"reactivePower": 100.1, // in var, can be null. Positive is injecting reactive power to the grid and negative is absorbing reactive power
"availableEnergy": 1000.1, // in Wh, can be null
"availableActivePower": {
"charge": 300.1, // in W, can be null
"discharge": 500.1 // in W, can be null
},
"stateOfCharge": 90.1, // in %, can be null.
"setpoints": {
"confirmed": { // configuration confirmed by the asset
"activePower": 142.5, // In W, can be null. Positive means discharging, negative charging.
"reactivePower": {
// Object defining reactive power control, can be null. Contains a mode and its corresponding setpoint.
// The mode determines which setpoint is relevant:
// - "fixedReactivePower" → uses "reactivePower" (in var).
// - "fixedPowerFactor" → uses "powerFactor" (unitless).
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
},
"deliverFcr": 100.1, // In W, can be null. Defines the max rate of the droop curve.
"chargeToPercentage": 50.1 // In %, can be null. Nonnegative.
},
"desired": { // setpoints from different sources
"activePower": { // In W, Positive means discharging, negative charging.
"cloud": 10000.5, // can be null
"activeControl": null, // can be null
"gridOperator": null, // can be null
"modbusServer": null, // can be null
"afrr":{
"delta": null, // In W, can be null. Contains portion of `deltaSetpoint` provided through the "applyAfrrDeltaSetpoint" API command
"reference": 10000.5, // In W. 0-minute reference value, to which the Teleport will apply the delta. This is the minimum of "availableActivePower" and all other active setpoints
"reference1MinuteLeadTime": 10000.5 // In W, can be null. 1-minute reference value. Only takes schedules sent in through the cloud and available power into account. Ramp rates and any local signals are not taken into account.
} // can be null
},
"reactivePower": { // has the same object structure as "confirmed.reactivePower"
"cloud": {
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
},
"gridOperator": { // has the same object structure as "confirmed.reactivePower"
"mode": "fixedPowerFactor", // can be "fixedReactivePower" or "fixedPowerFactor"
"powerFactor": 0.95 // Setpoint for "fixedPowerFactor" mode, unitless. Can be null.
// For capacitive loads (leading power factor, quadrants 2 and 4), the PF sign is positive.
// For inductive loads (lagging power factor, quadrants 1 and 3), the PF sign is negative.
},
"modbusServer": {
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
}
},
"chargeToPercentage": { // In %, Nonnegative.
"cloud": 50.1 // can be null
},
"deliverFcr": { // In W, Defines the max rate of the droop curve.
"cloud": 100.1, // can be null
"modbusServer": null // can be null
}
},
"effective": { // effective setpoint written by the Teleport
"activePower": 12100.3, // In W, can be null. Positive means discharging, negative charging.
"reactivePower": { // can be null. Has the same object structure as "confirmed.reactivePower"
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
},
"deliverFcr": null, // In W, can be null. Defines the max rate of the droop curve.
"fcr": {
"baseline": 0, // In W, can be null. Defines the FCR baseline (would have done without FCR-actions)
}
}
},
"scheduled": true // false for measurements that are not part of the regular reporting interval, eg. directly after command execution and at Teleport initialisation
}
]