"type": "batteryPower:2", // identifies this schema
"teleportHashId": "8de4y2", // uniquely identifies the teleport device
"assetIdentifier": "alfen-123", // globally unique identifier of the asset, when available the brand and serial number of the asset
"attempt": 0, // 0-indexed delivery attempt. integer
"isDeferred": false, // chronological ordering (by asset identifier) is only guaranteed for messages with isDeferred: false.
"measuredAt": "2023-01-01T00:00:00Z", // when read-out started, ISO 8601 yyyy-mm-ddThh:mm:ssZ or YYYYYY-MM-DDTHH:mm:ss.sssZ, so in UTC
"batteryStatus": "on", // can be "on", "off", "other" or null (see info and alarms in case of 'other')
"charged": 1000.2, // in Wh, can be null. Nonnegative
"discharged": 1000.3 // in Wh, can be null. Nonnegative
"frequency": 50.2, // in Hz, can be null. Nonnegative
"activePower": 1000.1, // in W, can be null. Positive means discharging, negative charging.
"reactivePower": 100.1, // in var, can be null. Positive is injecting reactive power to the grid and negative is absorbing reactive power
"powerFactor": 0.9, // unitless. Can be null. For capacitive loads (leading power factor, quadrants 2 and 4), the PF sign is positive. For inductive loads (lagging power factor, quadrants 1 and 3), the PF sign is negative.
"stateOfCharge": 90.1, // in %, can be null. Nonnegative
"stateOfHealth": 85.1, // in %, can be null. Nonnegative
"availableEnergy": 50.1, // in Wh, can be null. Nonnegative
"ratedEnergy": 1000.1, // in Wh, can be null. Nonnegative
"availableActivePower": {
"charge": 300.1, // in W, can be null. Nonnegative
"discharge": 500.1 // in W, can be null. Nonnegative
"availableReactivePower": {
"inject": 300.1, // in var, can be null. Nonnegative
"absorb": 500.1 // in var, can be null. Nonnegative
"activePower": 100.1, // in W, can be null. Positive means discharging, negative charging.
"deliverFcr": 100.1, // In W, can be null. Defines the max rate of the droop curve.
"chargeToPercentage": 20.1, // in W, can be null. Positive means discharging, negative charging.
"aggregate": 220.1 // in W, can be null. Positive means discharging, negative charging.
"threePhaseConnectionTypeHighVoltage": "delta", // can be "wye" or "delta", can be null
"acVoltageMediumVoltage": {
"l1": 230.4, // in V, can be null. Nonnegative
"l2": 230.1, // in V, can be null. Nonnegative
"l3": 230.2 // in V, can be null. Nonnegative
"l1": 230.4, // in V, can be null. Nonnegative
"l2": 230.1, // in V, can be null. Nonnegative
"l3": 230.2 // in V, can be null. Nonnegative
"acCurrentMediumVoltage": {
"l1": 11.4, // in A, can be null. Delivering to the grid is a positive value
"l2": 12.5, // in A, can be null. Delivering to the grid is a positive value
"l3": 10.1 // in A, can be null. Delivering to the grid is a positive value
"l1": 11.4, // in A, can be null. Delivering to the grid is a positive value
"l2": 12.5, // in A, can be null. Delivering to the grid is a positive value
"l3": 10.1 // in A, can be null. Delivering to the grid is a positive value
"active": -120.3, // in W, can be null. Negative means consuming, positive generating, will be negative or 0
"reactive": -28.4 // in Var, can be null. Negative means consuming, positive generating, will be negative or 0
"usableCapacity": { // in Wh, maximum amount of AC energy that is available from the battery for full charge/discharge taking into account SOC limits and efficiency
"chargeAtNominalPower": 7954545,
"dischargeAtNominalPower": 6942000,
"usableEnergy": { // in Wh, actual amount of AC energy available for charge/discharge at any moment taking into account SOC limits and efficiency
"chargeAtNominalPower": 1136364,
"dischargeAtNominalPower": 5162000,
"batteryEnergyStorageSystems": [
"identifier": "alfen-5678", // brand and serial number of the bess or if that's not available, its index
"min": 50.1, // in ºC, can be null, min value of all cells
"max": 50.1 // in ºC, can be null, max value of all cells
"roomTemperature": 30.1, // in ºC, can be null
"stateOfCharge": 50.1, // in %, can be null. Nonnegative
"availableEnergy": 1000.1, // in Wh, can be null. Nonnegative
"availableActivePower": {
"charge": 300.1, // in W, can be null. Nonnegative
"discharge": 500.1 // in W, can be null. Nonnegative
"threePhaseConnectionTypeLowVoltage": "wye", // can be "wye" or "delta", can be null
"l1": 230.4, // in V, can be null. Nonnegative
"l2": 230.1, // in V, can be null. Nonnegative
"l3": 230.2 // in V, can be null. Nonnegative
"l1": 230.4, // in V, can be null. Nonnegative
"l2": 230.1, // in V, can be null. Nonnegative
"l3": 230.2 // in V, can be null. Nonnegative
"l1": 11.4, // in A, can be null. Delivering to the grid is a positive value
"l2": 12.5, // in A, can be null. Delivering to the grid is a positive value
"l3": 10.1 // in A, can be null. Delivering to the grid is a positive value
"l1": 11.4, // in A, can be null. Delivering to the grid is a positive value
"l2": 12.5, // in A, can be null. Delivering to the grid is a positive value
"l3": 10.1 // in A, can be null. Delivering to the grid is a positive value
"identifier": "alfen-1", // brand and serial number of the rack or if that's not available, its index
"rackStatus": "on", // can be "on", "off", "other" or null (see info and alarms in case of 'other'),
"stateOfCharge": 90.1, // in %, can be null. Nonnegative
"dcVoltage": 12.5, // in V, can be null. Nonnegative
"dcCurrent": 23.5, // in A, can be null. Delivering to the grid is a positive value
"min": 30.1, // in ºC, can be null, min value of all cells in the rack
"cellIdMin": 19, // can be null, numeric ID of the cell with the lowest temperature in the rack
"max": 50.1, // in ºC, can be null, max value of all cells in the rack
"cellIdMax": 19 // can be null, numeric ID of the cell with the highest temperature in the rack
"min": 3.1, // in V, can be null, min value of all cells in the rack
"cellIdMin": 19, // can be null, numeric ID of the cell with the lowest voltage in the rack
"max": 4.1, // in V, can be null, max value of all cells in the rack
"cellIdMax": 19, // can be null, numeric ID of the cell with the highest voltage in the rack
"average": 3.6 // in V, can be null, average value of all cells in the rack
"warnings": ["ALFEN_SOME_WARNING_1", "ATEPS_SOME_WARNING_2"], // see error codes section (Deprecated: warning is an alias of info and will be removed in a future release)
"errors": ["ALFEN_SOME_ERROR_1"], // see error codes section (Deprecated:error is an alias of alarm and will be removed in a future release)
"info": ["ALFEN_SOME_WARNING_1", "ATEPS_SOME_WARNING_2"], // see error codes section
"alarms": ["ALFEN_SOME_ERROR_1"] // see error codes section
"confirmed": { // configuration confirmed by the asset
"activePower": 142.5, // In W, can be null. Positive means discharging, negative charging.
// Object defining reactive power control, can be null. Contains a mode and its corresponding setpoint.
// The mode determines which setpoint is relevant:
// - "fixedReactivePower" → uses "reactivePower" (in var).
// - "fixedPowerFactor" → uses "powerFactor" (unitless).
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
"deliverFcr": 100.1, // In W, can be null. Defines the max rate of the droop curve.
"chargeToPercentage": 50.1 // In %, can be null. Nonnegative.
"desired": { // setpoints from different sources
"activePower": { // In W, Positive means discharging, negative charging.
"cloud": 10000.5, // can be null
"activeControl": null, // can be null
"gridOperator": null, // can be null
"modbusServer": null, // can be null
"delta": null, // In W, can be null. Contains portion of `deltaSetpoint` provided through the "applyAfrrDeltaSetpoint" API command
"reference": 10000.5, // In W. 0-minute reference value, to which the Teleport will apply the delta. This is the minimum of "availableActivePower" and all other active setpoints
"reference1MinuteLeadTime": 10000.5 // In W, can be null. 1-minute reference value. Only takes schedules sent in through the cloud and available power into account. Ramp rates and any local signals are not taken into account.
"reactivePower": { // has the same object structure as "confirmed.reactivePower"
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
"gridOperator": { // has the same object structure as "confirmed.reactivePower"
"mode": "fixedPowerFactor", // can be "fixedReactivePower" or "fixedPowerFactor"
"powerFactor": 0.95 // Setpoint for "fixedPowerFactor" mode, unitless. Can be null.
// For capacitive loads (leading power factor, quadrants 2 and 4), the PF sign is positive.
// For inductive loads (lagging power factor, quadrants 1 and 3), the PF sign is negative.
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
"chargeToPercentage": { // In %, Nonnegative.
"cloud": 50.1 // can be null
"deliverFcr": { // In W, Defines the max rate of the droop curve.
"cloud": 100.1, // can be null
"modbusServer": null // can be null
"effective": { // effective setpoint written by the Teleport
"activePower": 12100.3, // In W, can be null. Positive means discharging, negative charging.
"reactivePower": { // Can be null. Has the same object structure as "confirmed.reactivePower"
"mode": "fixedReactivePower", // Reactive power control mode, either "fixedReactivePower" or "fixedPowerFactor".
"reactivePower": 13.2 // Setpoint for "fixedReactivePower" mode, in var. Can be null.
// Positive values inject reactive power into the grid, negative values absorb reactive power.
"deliverFcr": null, // In W, can be null. Defines the max rate of the droop curve.
"baseline": 0, // In W, can be null. Defines the FCR baseline (would have done without FCR-actions)
"info": ["ALFEN_SOME_WARNING_1", "ATEPS_SOME_WARNING_B"], // see error codes section
"alarms": ["ALFEN_SOME_ERROR_1"], // see error codes section
"errors": ["ALFEN_SOME_ERROR_1"], // see error codes section (Deprecated:error is an alias of alarm and will be removed in a future release)
"warnings": ["ALFEN_SOME_WARNING_1", "ATEPS_SOME_WARNING_B"], // see error codes section (Deprecated: warning is an alias of info and will be removed in a future release)
"scheduleCompleteUntil": "2023-01-01T00:00:00Z", // first gap in the schedule for this assetIdentifier. ISO 8601 yyyy-mm-ddThh:mm:ssZ or YYYYYY-MM-DDTHH:mm:ss.sssZ, so in UTC, can be null
"scheduled": true, // false for measurements that are not part of the regular reporting interval, eg. directly after command execution and at Teleport initialisation
"cellularSignalQuality": -55, // RSSI, in dBm, null means there is no up-to-date signal quality data, optional